Table of Contents
HPE Edge Center is a self-contained single rack modular, software-defined edge data center optimized to protect on-premises cloud, hybrid IT or IoT environments
It does this by edge enabling compute, network, storage, and control automation infrastructure. It has all the protection you need in an edge solution to have. It’s a complete enterprise IT data center that enables the flexibility to deploy computing where and when you need it while maintaining the efficiency, security, and control of your corporate data centers.
HPE Edge Center lets service providers expand or enter new geographies and markets without construction delays. And it enables them to provide IaaS on client premises, bringing their hosted cloud benefits to their client’s backyard while maintaining the economic benefits of cloud computing.
Overview
The initial HPE Edge Center secures and protects all infrastructure deployments, which drives down planning, acquisition, installation, and operations costs. It speeds deployment and streamlines operations by providing factory-integrated, pretested solutions designed for IoT and edge workloads.
Model 42E
HPE Edge Center Models
There are three models of the HPE Edge Center to meet the differing infrastructure needs. The three models share most of the same features but differ in resiliency, usable space rack units (RU) and amount of power capacity. All share the same levels of facilities intelligence, integration and software defined characteristics. The three models are as follows:
- – Model 42E
- – Model 42
- – Model 23
Standard Features
Model Summary
The HPE Edge Center models are summarized below:
Model 42E is our full size cabinet offering that has enterprise redundant infrastructure
- – 2N Power and Cooling infrastructures allowing for concurrent maintainability
- – 8 kW of Power and Cooling Capacity
- – 42 RU EIA 19” universal roller rack enabled cabinet 1200 mm depth
- – 29 RU of usable space
Model 42 is our full size cabinet non-redundant offering
- – Single N non-redundant Power and Cooling infrastructures
- – 8 kW of Power and Cooling Capacity
- – 42 RU EIA 19” universal cabinet 1200 mm depth
- – 35 RU of usable space
Model 23 is our half cabinet non-redundant offering
- – Single N non-redundant Power and Cooling infrastructures
- – 3 kW of Power and Cooling Capacity
- – 23 RU EIA 19” built in cabinet 1200 mm depth
- – 19 RU of usable space
Integrated Remote Management Of IT Systems And Facilities
HPE Edge Center integrates data center infrastructure management (DCIM) with HPE OneView IT infrastructure management to provide a single management interface with consolidated event management and a converged view of IT components and facilities from your central operations center. DCIM provides real-time management and control through the use of intelligent power and cooling. Sensors detect and report environmental conditions, fire detection and suppression events, physical security, water encroachment, and other conditions.
This integration of intelligent IT and facilities infrastructures enables management automation creating a software-defined facility. This management solution simplifies edge operations in a lights-out environment and enables seamless infrastructure provisioning and cloud management.
Key Features
International models available in either 60 hertz (hz) or 50 Hz single phase or three phase power configurations for worldwide power acceptance.
Model 23
HPE Edge Center Features
The HPE Edge Center models share many of the same characteristics which are outlined below:
- Structure
- – EIA 19” rack 1200 mm depth
- – Thermally rated and structurally reinforced
- – Extremely robust construction
- – Protection against water and dust with an elastomeric seal fitted all over the door panel into the door frames
- – Fire protection: Novec 1230 gas fire suppression system
- – Castor wheels
- – Earth-bonding point fitted on the top side of the rack
- – Cable gland for data/power, mounted at the bottom of the rack with capacity for 50 UTP cables
- – Indoor unit (Temperature range for cooling system -10 to 45 ºC)
- Doors
- – Front and back doors swing 180 degree
- – Heavy duty steel hinges on the left side of doors
- – The door design minimizes potential water and dust entry (NEMA-3R)
- – Double metal panel construction with a layer of insulation material in between
- – The mechanical lock has four locking points to ensure a tight closing, physical security against vandalism and reduced deformation if the door is exposed to very high temperatures
- Installation and Maintenance
- – All models come with a one-year onsite warranty and maintenance package
- – One and three year warranty and maintenance service extensions are available
- – Structure fully assembled in factory with interior cabling
- – The 42 models are available in Flat Pack for onsite delivery and assembly for restricted access sites
- – The 42 Models Structure can be broken down and reassembled on site
- – Wood pallet base, protected sides protected with bubble wrap roll and plastic foil
- – High resistant steel M20 eyebolts for elevation and transportation of the HPE Edge Center
- – Removable side panels for InRow cooling unit maintenance
- – Front door for access and back panel for an easy maintenance
- Facilities Monitoring
- – Monitoring unit NetBotz 570 with temperature, humidity, water, intrusion and smoke sensors
- – External CCTV Camera Pod 160
- – 24 Port 10/100/1000 Ethernet Switch
- – Leak detection rope or sensors
- – StruxureWare DCIM DCO and DCE with Intel DCM and Capacity Manager HPE Edge Center bundle included with one-year maintenance and support contract (warranty extensions are available)
- Security and Access Control
- – Electronic lock and NetBotz rack access handle on front and rear doors
- – Model 42E front door keypad access
- – Model 42 and 23 front access HID proximity cards
HPE Factory Express
One of the key features of the HPE Edge Center product line is the ability for IT infrastructures to be factory installed by HPE Factory Express Integration and Lifecycle services. HPE Factory Express Customer Designed Solution Integration Service provides integration with onsite start-up, along with the ability to specify more detailed configurations. The benefits of using Factory Express with the HPE Edge Center is by proving business agility allowing for faster adoption of solutions, mitigating risk of deployments based upon HPE’s vast deployment experience and the ability to manage costs by freeing up valuable resources.
Technical Specifications
| External Dimensions | Model 42E | Model 42 | Model 23* | | |||
|---|---|---|---|---|---|---|---|
| Width | 1,400 mm | 55 in | 1,100 mm | 43.3 in | 820 mm | 32.3 in | |
| Depth | 1,600 mm | 63 in | 1,600 mm | 63 in | 1,448 mm | 57 in | |
| Height | 2,360 mm | 96 in | 2,360 mm | 96 in | 2,146 mm | 84 in | |
| Weight (including cooling unit/UPS) | 1,181 kg | 2,603 lb | 850 kg | 1874 lb | 680 kg | 1500 lb | |
Power Specifications Summary
Model 42E Power
- – 208 – 240 VAC, 1 Phase, 60 Hz and 220 - 240VAC, 3Phase, 50 Hz
- – Internal power panel with circuit breaker protection
- – 4 x Switched, Metered, and Zero U Network Enabled PDU’s
- – Rack mounted network enabled UPS units with VRLA batteries with 5 minutes of runtime at maximum load
- – Maintenance-free sealed leak-proof batteries
- – (84) C13 (12) C19
Model 42 Power
- – 208 – 240 VAC, 1 Phase, 60 Hz and 220 - 240VAC, 1Phase, 50 Hz
- – Internal power panel with circuit breaker protection
- – 2 x Switched, Metered, and Zero U Network Enabled PDU’s
- – Rack mounted network enabled UPS units with VRLA batteries with 5 minutes of runtime at maximum load
- – Maintenance-free sealed leak-proof batteries
- – (42) C13 (6) C19
Model 23 Power
- – 208 – 240 VAC, 1 Phase, 60 Hz and 220 - 240VAC, 1 Phase, 50 Hz
- – Internal power panel with circuit breaker protection
- – 2 x Switched, Metered, and Zero U Network Enabled PDU’s
- – Rack mounted network enabled UPS units with VRLA batteries with 5 minutes of runtime at maximum load
- – Maintenance-free sealed leak-proof batteries
- – (14) C13 (2) C19
Cooling Specifications
Model 42E and 42
- – Self-Contained precision DX cooling with external condensers
- – Model 42E utilizes dual external condensers and Model 42 utilizes a single external condenser
- – InRow cooling units include flooded receiver, external condensers and cable-gland at the bottom of the HPE Edge Center for piping connections
- – Installation of external condensers and external piping not included
- – Drainage pipe locations are piped out the bottom of the unit requiring a drain for indoor applications
Model 23
- – Cooling infrastructure is self-contained top mounted precision DX with internal condenser
- – Drainage pipe locations are gravity fed from the top of the unit requiring a drain for indoor applications
Component Technical specifications
Cooling InRow Unit for Model 42E and 42
InRow RD Air-Cooled, Row-based, direct expansion cooling solutions for
wiring closets, server rooms, and data centers.
Includes Installation guide and, Operations and maintenance manual
| General Technical Specifications | |
| Cooling Capacity | 9.69 kW |
| Cooling Type | Air |
| Compressor Type | Scroll |
| Air Discharge Patterns | Horizontal |
| Intake Air | Rear Return |
| Refrigerant | R410A |
| Air Flow | 2290 CFM |
| Condensate Pump Capacity | 2.60 gal/hour |
| Input | |
| Nominal Input Power | 4400 Watts |
| Rack Height | 42U |
| Communication & Management | |
| Control panel | Multi-function LCD status and control console |
| Audible Alarm | Audible and visible alarms prioritized by severity |
| Physical | |
| Maximum Height | 1991.00 mm |
| Maximum Width | 300.00 mm |
| Maximum Depth | 1070.00 mm |
| Net Weight | 183.64 kg |
| Conformance | |
| Regulatory Approvals: | CUL Listed, C-tick, CE, UL Listed Standard |
External Condenser*for Model 42E and 42
50 hertz condenser 2 Fan, Single Circuit, 2.3MBH/1C TD, 400/3/50 FSC Model APC ACCD75219
60 hertz condenser 1Fan, Single Circuit, 2.3MBH/1C TD, 220/1/60 FSC Model APC ACCD75215*
Notes: *Please note that number of condensers is based upon the model (Model 42E dual condensers, Model 42 single condenser)
Top Mount Cooling for Model 23
- − Single Top mount DX cooling unit with internal condenser
- − Includes self-contained internal condenser
- − Nominal total cooling capacity: 3.8 kW
- − IT Available cooling capacity: 3.8 kW
- − Drain for condensate required and piping is not included
- − Includes cabling and circuit breaker protection
- − Regional cooling infrastructure subject to change but will maintain the minimum capacity and condenser configuration
| UPS Power Model 42E and 42 SmartUPS APC Smart- 8000VA RM 230 V APC Smart-UPS On-Line,8000 Watts /8000 VA, Output 208;240 V, Interface Port Contact Closure, RJ-45 10/100 Base-T, RJ-45 Serial, Smart-Slot, USB, Extended runtime model, Rack Height 6 | |
| Output | |
| Output Power Capacity | 8000 Watts / 8 kVA Max Configurable |
| Power | 8000 Watts / 8 kVA Nominal Output Voltage 230 V |
| Nominal Output Voltage | 208/220 V 50/60 Hz |
| Output Voltage Distortion | Less than 2% |
| Output Frequency (sync to mains) | 50/60 Hz +/- 3 |
| Hz Other Output Voltages | 240 V |
| Crest Factor | 3 : 1 |
| Topology | Double Conversion Online |
| Waveform Type | Sine wave |
| Output Connections | (1) Hard Wire 3-wire (H, N + G) (6) IEC 320 C13 (2) IEC 320 C19 (3) IEC Jumpers |
| Bypass | Internal Bypass (Automatic and Manual) |
| Batteries & Runtime Battery Type | Maintenance-free leak-proof sealed Lead-Acid battery with suspended |
| Typical Recharge time | 1.50 hour(s) |
| Communications & Management Interface Port(s) | Contact Closure, RJ-45 10/100 Base-T, RJ-45 Serial, Smart-Slot, USB |
| Interface Quantity | 1 |
| Control panel | Multi-function LCD status and control console |
| Audible Alarm | Audible and visible alarms prioritized by |
| UPS Power Model 23 SmartUPS APC Smart-UPS On-Line,4250 Watts /5000 VA, Output 208;240 V, Interface Port Contact Closure, RJ-45 10/100 Base-T, RJ-45 Serial, Smart-Slot, USB, Extended runtime model, Rack Height 3 U | |
| Output | |
| Output Power Capacity | 4250 Watts / 5 kVA Max Configurable |
| Power | 4250 Watts / 5 kVA |
| Nominal Output Voltage | 208/220 V 50/60 Hz |
| Output Voltage Distortion | Less than 2% |
| Output Frequency (sync to mains) | 50/60 Hz +/- 3 |
| Hz Other Output Voltages | 240 V |
| Crest Factor | 3 : 1 |
| Topology | Double Conversion Online |
| Waveform Type | Sine wave |
| Output Connections | (4) IEC 320 C13 (4) IEC 320 C19 (2) IEC Jumpers |
| Bypass | Internal Bypass (Automatic and Manual) |
| Batteries & Runtime Battery Type | Maintenance-free leak-proof sealed Lead-Acid battery with suspended |
| Typical Recharge time | 1.50 hour(s) |
| Communications & Management Interface Port(s) | Contact Closure, RJ-45 10/100 Base-T, RJ-45 Serial, Smart-Slot, USB |
| Interface Quantity | 1 |
| Control panel | Multi-function LCD status and control console |
| Audible Alarm | Audible and visible alarms prioritized by |
| Surge Protection and Filtering | |
| Surge energy rating | 480 Joules |
| Conformance | |
| Regulatory Approvals | C-tick, CE, CE Mark, EAC, EN 50091-1, EN 50091-2, ENERGY STAR (EU) IEC 60950, IEC 62040-2, IRAM, VDE |
| Model 42E and 42 Switched Rack PDU Model 42 - 2 x Rack PDU, 2G, Switched, Zero U, 20A, 208 V, (7) C13 & (1) C19 Model 42E - 4 x Rack PDU, 2G, Switched, Zero U, 20A, 208 V, (7) C13 & (1) C19 APC Switched Rack Power Distribution Units (PDUs) enable advanced, user-customizable power control and active monitoring. Remote outlet level controls allow power on/off functionality for power recycling to remotely reboot equipment and restrict unauthorized use of individual outlets. Power sequencing delays allow users to define the order in which to power up or down attached equipment. Avoid circuit overload during power recovery and extend uptime of critical equipment by prioritizing the load shedding. Current metering provides real-time remote monitoring of connected loads. Switched Rack PDUs include real power monitoring, a temperature/humidity sensor port, locking IEC receptacles, and low profile circuit breakers. User-defined alarms warn of potential circuit overloads before critical IT failures occur. Users can access, configure, and control Switched Rack PDUs through secure Web, SNMP, or Telnet Interfaces and is complimented by APC Centralized Management platforms using InfraStruxure Central, Capacity Manager and Change Manager. | |
| Output | |
| Nominal Output Voltage | 200 V, 240 V Maximum Total Current Draw per Phase 30A |
| Output Connections | (21) IEC 320 C13 (3) IEC 320 C19 |
| Overload Protection | No |
| Input | |
| Nominal Input Voltage | 200 V, 208 V, 230 V |
| Input Frequency | 50/60 Hz |
| Maximum Input Current per phase | 30A |
| Conformance | |
| Regulatory Approvals | CUL Listed, EN 55022 Class A, EN 55024 EN 61000-3-2, EN61000-3-3, FCC Part 15 Class A, ICES-003, PSE, UL Listed, VCCI Class A, VDE |
| Model 23 Switched Rack PDU 2 x Rack PDU, 2G, Switched, Zero U, 20A, 208 V, (7) C13 & (1) C19 APC Switched Rack Power Distribution Units (PDUs) enable advanced, user-customizable power control and active monitoring. Remote outlet level controls allow power on/off functionality for power recycling to remotely reboot equipment and restrict unauthorized use of individual outlets. Power sequencing delays allow users to define the order in which to power up or down attached equipment. Avoid circuit overload during power recovery and extend uptime of critical equipment by prioritizing the load shedding. Current metering provides real-time remote monitoring of connected loads. Switched Rack PDUs include real power monitoring, a temperature/humidity sensor port, locking IEC receptacles, and low profile circuit breakers. User-defined alarms warn of potential circuit overloads before critical IT failures occur. Users can access, configure, and control Switched Rack PDUs through secure Web, SNMP, or Telnet Interfaces and is complimented by APC Centralized Management platforms using InfraStruxure Central, Capacity Manager and Change Manager. | |
| Output | |
| Nominal Output Voltage | 200 V, 240 V Maximum Total Current Draw per Phase 20A |
| Output Connections | (7) IEC 320 C13 (1) IEC 320 C19 |
| Overload Protection | No |
| Input | |
| Nominal Input Voltage | 200 V, 208 V, 230 V |
| Input Frequency | 50/60 Hz |
| Maximum Input Current per phase | 20A |
| Conformance | |
| Regulatory Approvals | CUL Listed, EN 55022 Class A, EN 55024 EN 61000-3-2, EN61000-3-3, FCC Part 15 Class A, ICES-003, PSE, UL Listed, VCCI Class A, VDE |
Summary of External Input Panel Power Requirements
Input Power Requirements
- Model 42E Power Input Requirements
- Model 42E Power Input Requirements 60 Hz
- 200A/1P/200-220VAC/60h
- Model 42 Power Input Requirements 50 Hz
- 100A/1P/220-240VAC/50 Hz
- Model 42 Power Input Requirements 60 Hz
- 100A/1P/200-220VAC/60 Hz
- Model 23 Power Input Requirements 50 Hz
- 63A/1P/220-240VAC/50 Hz
- Model 23 Power Input Requirements 60 Hz
- 42A/1P/200-220VAC/60 Hz
Universal Technical Specifications
Cable Glands
One set of ROXTEC tight cable gland is mounted at the bottom of the cabinet.
The cable gland has a free space for mounting blocks for the different sizes of cables and pipes. Additional cable gland for InRow unit piping and drainage mounted at the bottom of the rack.
Cablegland performance:
- − Fire: Tested for fire integrity and insulation - “Fire Class A” certification
- − Smoke: Prevents the passage of smoke and fumes when exposed to fire
- − Explosion: Can withstand an explosion up to 23 bar without the seal integrity being exposed
- − Pressure: Tested with water and air up to 5 bar
- − Sound: Effectively dampens the sound transmission up to 53 db
- − Vibration: Capable of withstanding vibration 5-33 Hz without any detrimental effect to the system
- − Chemical Resistance: High degree of resistance to a variety of chemicals
- − Accelerate heat aging: Heat aging showed little deterioration of hardness, tensile strength or elongation at break
- − Gamma radiation: Subjected to 2x103 Rads of Gamma Radiation with no detrimental effect
- − Rodents: Subjected to rodents for 3 weeks without any sign of deterioration to the seal
Environmental Monitoring
- − APC NetBotz Rack monitor, Model 450 (Installed beside electrical power distribution panel) with ATS
- − Includes the following sensors: temperature, humidity and smoke
- − CCTV Camera Pod 160
- − NetBotz Spot Fluid Sensors
Casters
Addition of four casters which add 8.3” (210 mm) to the height of the overall solution. Total height replacing supporting legs 95.67” (2430 mm)
| Infrastructure and Software | |||
|---|---|---|---|
| Warranty | Notes | Description | SKU |
| Year | Requires Q1N11A, Q1N13A | HPE Edge Center 42E 60 Hz Solution | Q1N03A |
| Year | Requires Q1N13A | HPE Edge Center 42 60 Hz Solution | Q1N04A |
| Year | Requires Q1N13A | HPE Edge Center 23 60 Hz Solution | Q1N05A |
| Year | Requires Q1N11A, Q1N13A | HPE Edge Center 42E 50 Hz Solution | Q1N06A |
| Year | Requires Q1N13A | HPE Edge Center 42 50 Hz Solution | Q1N07A |
| Year | Requires Q1N13A | HPE Edge Center 23 50 Hz Solution | Q1N08A |
| N/A | N/A | HPE Edge Center Roller Rack | Q1N11A |
| Year | Required for all HPE Edge Centers | HPE Edge Center SDF Accelerator | Q1N13A |
Service and Support
HPE Services
No matter where you are in your digital transformation journey, you can count on HPE Services to deliver the expertise you need when, where and how you need it. From planning to deployment, ongoing operations and beyond, our experts can help you realize your digital ambitions.
Consulting Services
No matter where you are in your journey to hybrid cloud, experts can help you map out your next steps. From determining what workloads should live where, to handling governance and compliance, to managing costs, our experts can help you optimize your operations.
https://www.HPE.com/services/consulting
HPE Managed Services
HPE runs your IT operations, providing services that monitor, operate, and optimize your infrastructure and applications, delivered consistently and globally to give you unified control and let you focus on innovation.
Operational services
Optimize your entire IT environment and drive innovation. Manage day-to-day IT operational tasks while freeing up valuable time and resources. Meet service-level targets and business objectives with features designed to drive better business outcomes.
https://www.HPE.com/services/operational
HPE Complete Care Service
HPE Complete Care Service is a modular, edge-to-cloud IT environment service designed to help optimize your entire IT environment and achieve agreed upon IT outcomes and business goals through a personalized experience. All delivered by an assigned team of HPE Services experts. HPE Complete Care Service provides:
- − A complete coverage approach -- edge to cloud
- − An assigned HPE team
- − Modular and fully personalized engagement
- − Enhanced Incident Management experience with priority access
- − Digitally enabled and AI driven customer experience
https://www.HPE.com/services/completecare
HPE Tech Care Service
HPE Tech Care Service is the operational support service experience for HPE products. The service goes beyond traditional support by providing access to product specific experts, an AI driven digital experience, and general technical guidance to not only reduce risk but constantly search for ways to do things better. HPE Tech Care Service delivers a customer-centric, AI driven, and digitally enabled customer experience to move your business forward. HPE Tech Care Service is available in three response levels. Basic, which provides 9x5 business hour availability and a 2-hour response time. Essential which provides a 15-minute response time 24x7 for most enterprise level customers, and Critical which includes a 6-hour repair commitment where available and outage management response for severity 1 incidents.
HPE Lifecycle Services
HPE Lifecycle Services provide a variety of options to help maintain your HPE systems and solutions at all stages of the product lifecycle. A few popular examples include:
- − Lifecycle Install and Startup Services: Various levels for physical installation and power on, remote access setup, installation and startup, and enhanced installation services with the operating system.
- − HPE Firmware Update Analysis Service: Recommendations for firmware revision levels for selected HPE products, taking into account the relevant revision dependencies within your IT environment.
- − HPE Firmware Update Implementation Service: Implementation of firmware updates for selected HPE server, storage, and solution products, taking into account the relevant revision dependencies within your IT environment.
- − Implementation assistance services: Highly trained technical service specialists to assist you with a variety of activities, ranging from design, implementation, and platform deployment to consolidation, migration, project management, and onsite technical forums.
- − HPE Service Credits: Access to prepaid services for flexibility to choose from a variety of specialized service activities, including assessments, performance maintenance reviews, firmware management, professional services, and operational best practices.
Notes: To review the list of Lifecycle Services available for your product go to: https://www.HPE.com/services/lifecycle
For a list of the most frequently purchased services using service credits, see the HPE Service Credits Menu
Other Related Services from HPE Services:
HPE Education Services
Training and certification designed for IT and business professionals across all industries. Broad catalogue of course offerings to expand skills and proficiencies in topics ranging from cloud and cybersecurity to AI and DevOps. Create learning paths to expand proficiency in a specific subject. Schedule training in a way that works best for your business with flexible continuous learning options.
https://www.HPE.com/services/training
Defective Media Retention
An option available with HPE Complete Care Service and HPE Tech Care Service and applies only to Disk or eligible SSD/Flash Drives replaced by HPE due to malfunction.
Consult your HPE Sales Representative or Authorized Channel Partner of choice for any additional questions and services options.
Parts and Materials
HPE will provide HPE-supported replacement parts and materials necessary to maintain the covered hardware product in operating condition, including parts and materials for available and recommended engineering improvements.
Parts and components that have reached their maximum supported lifetime and/or the maximum usage limitations as set forth in the manufacturer's operating manual, product quick-specs, or the technical product data sheet will not be provided, repaired, or replaced as part of these services.
How to Purchase Services
Services are sold by Hewlett Packard Enterprise and Hewlett Packard Enterprise Authorized Service Partners:
- − Services for customers purchasing from HPE or an enterprise reseller are quoted using HPE order configuration tools.
- − Customers purchasing from a commercial reseller can find services at https://ssc.HPE.com/portal/site/ssc/
AI Powered and Digitally Enabled Support Experience
Achieve faster time to resolution with access to product-specific resources and expertise through a digital and data driven customer experience
Sign into the HPE Support Center experience, featuring streamlined self-serve case creation and management capabilities with inline knowledge recommendations. You will also find personalized task alerts and powerful troubleshooting support through an intelligent virtual agent with seamless transition when needed to a live support agent.
https://support.HPE.com/hpesc/public/home/signin
Consume IT On Your Terms
HPE GreenLake edge-to-cloud platform brings the cloud experience directly to your apps and data wherever they are—the edge, colocations, or your data center. It delivers cloud services for on-premises IT infrastructure specifically tailored to your most demanding workloads. With a pay-per-use, scalable, point-and-click self-service experience that is managed for you, HPE GreenLake edge-to-cloud platform accelerates digital transformation in a distributed, edge-to-cloud world.
- − Get faster time to market
- − Save on TCO, align costs to business
- − Scale quickly, meet unpredictable demand
- − Simplify IT operations across your data centers and clouds
To learn more about HPE Services, please contact your Hewlett Packard Enterprise sales representative or Hewlett Packard Enterprise Authorized Channel Partner. Contact information for a representative in your area can be found at "Contact HPE" https://www.HPE.com/us/en/contact-HPE.html
For more information
Summary of Changes
| Date | Version History | Action | Description of Change: |
|---|---|---|---|
| 16-Feb-2026 | Changed | Visual rebranding only—updated typography, colors, and design elements to align with new HPE brand standards. No technical specifications or content were modified. | |
| 08-Jan-2024 | Changed | HPE Services Rebranding | |
| 15-Nov-2021 | Changed | Service and Support section was updated. | |
| 15-Oct-2018 | Changed | Overview, Technical Specification, Standard Features and Warranty sections were updated. QuickSpecs Name changed from HPE Micro Datacenter to HPE Edge Center | |
| 28-Nov-2016 | New | New QuickSpecs |
© Copyright 2026 Hewlett Packard Enterprise Development LP. The information contained herein is subject to change without notice. The only warranties for Hewlett Packard Enterprise products and services are set forth in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty. Hewlett Packard Enterprise shall not be liable for technical or editorial errors or omissions contained herein.